OpenStudio Results
Model Summary
| Information | Value | Units |
|---|---|---|
| Building Name | NECB 2011-SmallHotel-NECB HDD Method-CAN_MB_Churchill.719130_CWEC.epw created: 2017-06-30 16:29:08 +0000 | building_name |
| Net Site Energy | 4,388,298 | kBtu |
| Total Building Area | 43,202 | ft^2 |
| EUI (Based on Net Site Energy and Total Building Area) | 101.58 | kBtu/ft^2 |
| OpenStudio Standards Building Type | SmallHotel |
| Value | |
|---|---|
| Weather File | Churchill MB CAN WYEC2-B-15901 WMO#=719130 |
| Latitude | 58.75 |
| Longitude | -94.1 |
| Elevation | 95 (ft) |
| Time Zone | -6.0 |
| North Axis Angle | 180.00 |
| ASHRAE Climate Zone |
| Maximum Dry Bulb (F) | Daily Temperature Range (R) | Humidity Value | Humidity Type | Wind Speed (mph) | Wind Direction | |
|---|---|---|---|---|---|---|
| CHURCHILL ANN CLG .4% CONDNS DB=>MWB | 78.26 | 17.82 | 63.32 | Wetbulb [F] | 12.3 | 210.0 |
| CHURCHILL ANN CLG .4% CONDNS WB=>MDB | 74.84 | 17.82 | 64.94 | Wetbulb [F] | 12.3 | 210.0 |
| CHURCHILL ANN HTG 99.6% CONDNS DB | -36.58 | 0.0 | -36.58 | Wetbulb [F] | 12.3 | 290.0 |
| Time Setpoint Not Met | Time (hr) |
|---|---|
| During Heating | 137.25 |
| During Cooling | 1.0 |
| During Occupied Heating | 125.25 |
| During Occupied Cooling | 1.0 |
| Tolerance for Time Setpoint Not Met | Temperature (F) |
|---|---|
| Heating | 1.8 |
| Cooling | 1.8 |
Annual Overview
One or more tables in Annual Overview section returned false and was skipped.
| End Use | Consumption (kBtu) |
|---|---|
| Heating | 2,610,203 |
| Cooling | 18,094 |
| Interior Lighting | 372,615 |
| Exterior Lighting | 0 |
| Interior Equipment | 93,379 |
| Exterior Equipment | 0 |
| Fans | 165,366 |
| Pumps | 1,327 |
| Heat Rejection | 28 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 1,127,286 |
| Refrigeration | 0 |
| Generators | 0 |
| Fuel | Consumption (kBtu) |
|---|---|
| Electricity | 4,388,298 |
| Natural Gas | 0 |
| Additional Fuel | 0 |
| District Cooling | 0 |
| District Heating | 0 |
| End Use | Consumption (kWh) |
|---|---|
| Heating | 764,975 |
| Cooling | 5,303 |
| Interior Lighting | 109,203 |
| Exterior Lighting | 0 |
| Interior Equipment | 27,367 |
| Exterior Equipment | 0 |
| Fans | 48,464 |
| Pumps | 389 |
| Heat Rejection | 8 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 330,375 |
| Refrigeration | 0 |
| Generators | 0 |
Monthly Overview
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 117394.44 | 114575.0 | 99460.56 | 68937.22 | 44054.44 | 24199.56 | 11607.44 | 13182.58 | 24584.14 | 50964.17 | 75935.56 | 120078.61 | 764973.72 |
| Cooling | 17.8 | 16.32 | 16.39 | 26.36 | 71.92 | 878.82 | 2287.98 | 1621.21 | 292.63 | 43.12 | 12.2 | 18.56 | 5303.3 |
| Interior Lighting | 9274.53 | 8378.94 | 9308.33 | 8924.72 | 9308.33 | 8998.53 | 9234.53 | 9308.33 | 8958.56 | 9274.53 | 8998.53 | 9234.53 | 109202.39 |
| Exterior Lighting | |||||||||||||
| Interior Equipment | 2324.35 | 2099.92 | 2335.12 | 2232.89 | 2335.12 | 2256.72 | 2311.29 | 2335.12 | 2243.66 | 2324.35 | 2256.72 | 2311.29 | 27366.55 |
| Exterior Equipment | |||||||||||||
| Fans | 3967.44 | 3584.86 | 3963.11 | 3832.19 | 4000.42 | 4115.44 | 4701.94 | 4519.58 | 3993.08 | 3988.14 | 3832.22 | 3965.92 | 48464.36 |
| Pumps | 23.91 | 21.69 | 20.42 | 18.6 | 21.52 | 42.24 | 78.32 | 65.85 | 33.06 | 20.63 | 19.36 | 24.21 | 389.79 |
| Heat Rejection | 0.0 | 0.0 | 0.01 | 0.01 | 0.04 | 1.63 | 3.56 | 3.13 | 0.31 | 0.05 | 0.02 | 0.0 | 8.78 |
| Humidification | |||||||||||||
| Heat Recovery | |||||||||||||
| Water Systems | 28035.56 | 25347.11 | 28090.28 | 27113.17 | 28090.56 | 27175.39 | 28026.39 | 28090.83 | 27165.03 | 28037.78 | 27175.81 | 28027.5 | 330375.39 |
| Refrigeration | |||||||||||||
| Generators | |||||||||||||
| Total | 161038.03 | 154023.84 | 143194.21 | 111085.17 | 87882.34 | 67668.33 | 58251.46 | 59126.64 | 67270.47 | 94652.76 | 118230.4 | 163660.62 | 1286084.28 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 265.8902 | 290.8069 | 281.3867 | 249.9866 | 150.7604 | 97.9773 | 44.0406 | 51.1579 | 87.5011 | 191.5608 | 230.9683 | 291.066 |
| Cooling | 0.0259 | 0.0343 | 0.07 | 0.0532 | 0.0418 | 0.0069 | ||||||
| Interior Lighting | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 |
| Exterior Lighting | ||||||||||||
| Interior Equipment | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 |
| Exterior Equipment | ||||||||||||
| Fans | 5.4947 | 5.4947 | 5.4947 | 5.4947 | 5.4947 | 5.4947 | 5.5926 | 5.5937 | 5.5145 | 5.4947 | 5.4947 | 5.4947 |
| Pumps | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.0187 |
| Heat Rejection | ||||||||||||
| Humidification | ||||||||||||
| Heat Recovery | ||||||||||||
| Water Systems | 70.9084 | 73.7991 | 70.2086 | 71.911 | 75.5814 | 75.5821 | 75.3741 | 75.5815 | 75.5815 | 75.0424 | 71.0947 | 75.4786 |
| Refrigeration | ||||||||||||
| Generators | ||||||||||||
| Total | 364.2 | 392.01 | 379.0 | 349.3 | 253.77 | 200.99 | 146.98 | 154.29 | 190.55 | 294.01 | 329.46 | 393.95 |
Utility Bills/Rates
No Data to Show for Utility Bills/Rates
Envelope
| Construction | Net Area (ft^2) | Surface Count | R Value (ft^2*h*R/Btu) |
|---|---|---|---|
| Customized opaque construction {1a6ee2e2-5af1-4d07-87ad-8fe6105039fa} to conductance of 0.142 | 10,800 | 16 | 39.99 |
| Customized opaque construction {e9b04795-ed11-4744-8eaf-105aae4bafd9} to conductance of 0.183 | 16,258 | 92 | 31.03 |
| Construction | Area (ft^2) | Surface Count | U-Factor (Btu/ft^2*h*R) |
|---|---|---|---|
| Customized Fenestration: cond=0.160 tvis=0.220 tsol=0.232 | 1,983 | 103 | 0.2818 |
| Description | Total (%) | North (%) | East (%) | South (%) | West (%) |
|---|---|---|---|---|---|
| Gross Window-Wall Ratio | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Gross Window-Wall Ratio (Conditioned) | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Skylight-Roof Ratio | 0.0 |
Space Type Breakdown
| Space Type Name | Floor Area (ft^2) | Standards Building Type | Standards Space Type |
|---|---|---|---|
| Space Function Corr. >= 2.4m wide-sch-F | 5,670 | Space Function | Corr. >= 2.4m wide-sch-F |
| Space Function Electrical/Mechanical-sch-F | 1,215 | Space Function | Electrical/Mechanical-sch-F |
| Space Function Gym - fitness | 351 | Space Function | Gym - fitness |
| Space Function Hotel/Motel - lobby | 1,755 | Space Function | Hotel/Motel - lobby |
| Space Function Hway lodging - rooms | 27,271 | Space Function | Hway lodging - rooms |
| Space Function Lobby - elevator | 648 | Space Function | Lobby - elevator |
| Space Function Lounge/recreation | 351 | Space Function | Lounge/recreation |
| Space Function Office - enclosed | 1,404 | Space Function | Office - enclosed |
| Space Function Stairway-sch-F | 1,728 | Space Function | Stairway-sch-F |
| Space Function Storage area - occsens | 2,457 | Space Function | Storage area - occsens |
| Space Function Washroom-sch-F | 351 | Space Function | Washroom-sch-F |
Space Type Summary
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Corr. >= 2.4m wide-sch-F People Definition | 0.0009 | people/ft^2 | 1.0 |
| Space Function Corr. >= 2.4m wide-sch-F Lights Definition | 0.6596 | W/ft^2 | 1.0 |
| Space Function Corr. >= 2.4m wide-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Electrical/Mechanical-sch-F People Definition | 0.0005 | people/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Lights Definition | 1.2356 | W/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Gym - fitness People Definition | 0.0186 | people/ft^2 | 1.0 |
| Space Function Gym - fitness Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Gym - fitness Lights Definition | 0.9104 | W/ft^2 | 1.0 |
| Space Function Gym - fitness Ventilation (outdoor air method Sum) | 0.8600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Hotel/Motel - lobby People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Elec Equip Definition | 0.2323 | W/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Lights Definition | 1.0591 | W/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Ventilation (outdoor air method Sum) | 0.2850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Hway lodging - rooms People Definition | 0.0037 | people/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Elec Equip Definition | 0.2323 | W/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Lights Definition | 0.7525 | W/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Ventilation (outdoor air method Sum) | 0.1100 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Lobby - elevator People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Lobby - elevator Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Lobby - elevator Lights Definition | 0.6410 | W/ft^2 | 1.0 |
| Space Function Lobby - elevator Ventilation (outdoor air method Sum) | 0.8100 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Lounge/recreation People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Lounge/recreation Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Lounge/recreation Lights Definition | 0.7860 | W/ft^2 | 1.0 |
| Space Function Lounge/recreation Ventilation (outdoor air method Sum) | 0.1850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Office - enclosed People Definition | 0.0046 | people/ft^2 | 1.0 |
| Space Function Office - enclosed Elec Equip Definition | 0.6968 | W/ft^2 | 1.0 |
| Space Function Office - enclosed Lights Definition | 1.1055 | W/ft^2 | 1.0 |
| Space Function Office - enclosed Ventilation (outdoor air method Sum) | 0.0850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Stairway-sch-F People Definition | 0.0005 | people/ft^2 | 1.0 |
| Space Function Stairway-sch-F Lights Definition | 0.6875 | W/ft^2 | 1.0 |
| Space Function Stairway-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Storage area - occsens People Definition | 0.0009 | people/ft^2 | 1.0 |
| Space Function Storage area - occsens Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Storage area - occsens Lights Definition | 0.5686 | W/ft^2 | 1.0 |
| Space Function Storage area - occsens Ventilation (outdoor air method Sum) | 0.0700 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Washroom-sch-F People Definition | 0.0031 | people/ft^2 | 1.0 |
| Space Function Washroom-sch-F Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Washroom-sch-F Lights Definition | 0.8779 | W/ft^2 | 1.0 |
| Space Function Washroom-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
Interior Lighting Summary
| Zone | Lighting Power Density (W/ft^2) | Total Power (W) | Schedule Name | Scheduled Hours/Week (hr) | Actual Load Hours/Week (hr) | Return Air Fraction | Annual Consumption (kWh) | |
|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.66 | 1068.58 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3180.56 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION ELECTRICAL/MECHANICAL-SCH-F LIGHTS | SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1.24 | 433.73 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 1291.67 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION ELECTRICAL/MECHANICAL-SCH-F LIGHTS | SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1.24 | 1067.63 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3177.78 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN SPACE FUNCTION GYM - FITNESS LIGHTS | SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0.91 | 319.57 | NECB-B-LIGHTING | 103.58 | 103.57 | 0.0000 | 1725.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN SPACE FUNCTION HOTEL/MOTEL - LOBBY LIGHTS | SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1.06 | 1858.83 | NECB-H-LIGHTING | 151.2 | 151.2 | 0.0000 | 14655.56 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN SPACE FUNCTION LOUNGE/RECREATION LIGHTS | SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0.79 | 275.87 | NECB-B-LIGHTING | 103.58 | 103.57 | 0.0000 | 1488.89 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN SPACE FUNCTION OFFICE - ENCLOSED LIGHTS | SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1.11 | 1552.17 | NECB-A-LIGHTING | 56.27 | 56.27 | 0.0000 | 4552.78 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.57 | 598.7 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 1711.11 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION WASHROOM-SCH-F LIGHTS | SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.88 | 308.17 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 916.67 |
Plug Loads Summary
| Electricity Annual Value (kWh) | |
|---|---|
| InteriorEquipment:Electricity:Zone:SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 97.22 |
| InteriorEquipment:Electricity:Zone:SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 238.89 |
| InteriorEquipment:Electricity:Zone:SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 175.0 |
| InteriorEquipment:Electricity:Zone:SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 3213.89 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 175.0 |
| InteriorEquipment:Electricity:Zone:SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 3622.22 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 280.56 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 97.22 |
Exterior Lighting
No Data to Show for Exterior Lighting
Water Use Equipment
| Instance | Plant Loop | Definition | Space | Peak Flow Rate (gal/min) | Flow Rate Schedule | Target Temp Range (F) |
|---|---|---|---|---|---|---|
| Employeeloungeflr1 Service Water Use 0.02gal/min | Main Service Water Loop | Employeeloungeflr1 Service Water Use Def 0.02gal/min | EmployeeLoungeFlr1 | 0.02 | NECB-B-Service Water Heating | 140.0 to 140.0 |
| Exercisecenterflr1 Service Water Use 0.05gal/min | Main Service Water Loop | Exercisecenterflr1 Service Water Use Def 0.05gal/min | ExerciseCenterFlr1 | 0.05 | NECB-B-Service Water Heating | 140.0 to 140.0 |
| Frontloungeflr1 Service Water Use 0.04gal/min | Main Service Water Loop | Frontloungeflr1 Service Water Use Def 0.04gal/min | FrontLoungeFlr1 | 0.04 | NECB-H-Service Water Heating | 140.0 to 140.0 |
| Frontofficeflr1 Service Water Use 0.05gal/min | Main Service Water Loop | Frontofficeflr1 Service Water Use Def 0.05gal/min | FrontOfficeFlr1 | 0.05 | NECB-A-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr1 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr1 Service Water Use Def 0.0gal/min | FrontStorageFlr1 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr2 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr2 Service Water Use Def 0.0gal/min | FrontStorageFlr2 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr3 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr3 Service Water Use Def 0.0gal/min | FrontStorageFlr3 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr4 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr4 Service Water Use Def 0.0gal/min | FrontStorageFlr4 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Guestroom101 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom101 Service Water Use Def 0.07gal/min | GuestRoom101 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom102 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom102 Service Water Use Def 0.07gal/min | GuestRoom102 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom103 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom103 Service Water Use Def 0.07gal/min | GuestRoom103 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom104 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom104 Service Water Use Def 0.07gal/min | GuestRoom104 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom105 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom105 Service Water Use Def 0.07gal/min | GuestRoom105 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom201 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom201 Service Water Use Def 0.07gal/min | GuestRoom201 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom202_205 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom202_205 Service Water Use Def 0.27gal/min | GuestRoom202_205 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom206_208 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom206_208 Service Water Use Def 0.22gal/min | GuestRoom206_208 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom209_212 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom209_212 Service Water Use Def 0.27gal/min | GuestRoom209_212 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom213 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom213 Service Water Use Def 0.07gal/min | GuestRoom213 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom214 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom214 Service Water Use Def 0.07gal/min | GuestRoom214 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom215_218 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom215_218 Service Water Use Def 0.27gal/min | GuestRoom215_218 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom219 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom219 Service Water Use Def 0.07gal/min | GuestRoom219 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom220_223 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom220_223 Service Water Use Def 0.27gal/min | GuestRoom220_223 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom224 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom224 Service Water Use Def 0.07gal/min | GuestRoom224 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom301 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom301 Service Water Use Def 0.07gal/min | GuestRoom301 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom302_305 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom302_305 Service Water Use Def 0.27gal/min | GuestRoom302_305 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom306_308 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom306_308 Service Water Use Def 0.22gal/min | GuestRoom306_308 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom309_312 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom309_312 Service Water Use Def 0.27gal/min | GuestRoom309_312 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom313 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom313 Service Water Use Def 0.07gal/min | GuestRoom313 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom314 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom314 Service Water Use Def 0.07gal/min | GuestRoom314 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom315_318 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom315_318 Service Water Use Def 0.27gal/min | GuestRoom315_318 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom319 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom319 Service Water Use Def 0.07gal/min | GuestRoom319 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom320_323 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom320_323 Service Water Use Def 0.27gal/min | GuestRoom320_323 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom324 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom324 Service Water Use Def 0.07gal/min | GuestRoom324 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom401 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom401 Service Water Use Def 0.07gal/min | GuestRoom401 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom402_405 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom402_405 Service Water Use Def 0.27gal/min | GuestRoom402_405 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom406_408 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom406_408 Service Water Use Def 0.22gal/min | GuestRoom406_408 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom409_412 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom409_412 Service Water Use Def 0.27gal/min | GuestRoom409_412 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom413 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom413 Service Water Use Def 0.07gal/min | GuestRoom413 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom414 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom414 Service Water Use Def 0.07gal/min | GuestRoom414 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom415_418 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom415_418 Service Water Use Def 0.27gal/min | GuestRoom415_418 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom419 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom419 Service Water Use Def 0.07gal/min | GuestRoom419 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom420_423 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom420_423 Service Water Use Def 0.27gal/min | GuestRoom420_423 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom424 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom424 Service Water Use Def 0.07gal/min | GuestRoom424 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Laundryroomflr1 Service Water Use 0.03gal/min | Main Service Water Loop | Laundryroomflr1 Service Water Use Def 0.03gal/min | LaundryRoomFlr1 | 0.03 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr1 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr1 Service Water Use Def 0.01gal/min | RearStorageFlr1 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr2 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr2 Service Water Use Def 0.01gal/min | RearStorageFlr2 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr3 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr3 Service Water Use Def 0.01gal/min | RearStorageFlr3 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr4 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr4 Service Water Use Def 0.01gal/min | RearStorageFlr4 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
HVAC Load Profiles
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Average Outdoor Air Dry Bulb (F) | -10.1 | -14.5 | -3.7 | 12.0 | 29.9 | 41.7 | 53.4 | 52.0 | 41.9 | 28.4 | 10.2 | -10.1 |
| Cooling Load (MBtu) | 0.06 | 0.06 | 0.06 | 0.09 | 0.25 | 3.0 | 7.81 | 5.53 | 1.0 | 0.15 | 0.04 | 0.06 |
| Heating Load (MBtu) | 400.57 | 390.95 | 339.37 | 235.22 | 150.32 | 82.57 | 39.61 | 44.98 | 83.88 | 173.9 | 259.1 | 409.73 |
Zone Conditions
| Zone | Unmet Htg (hr) | Unmet Htg - Occ (hr) | < 56 (F) | 56-61 (F) | 61-66 (F) | 66-68 (F) | 68-70 (F) | 70-72 (F) | 72-74 (F) | 74-76 (F) | 76-78 (F) | 78-83 (F) | 83-88 (F) | >= 88 (F) | Unmet Clg (hr) | Unmet Clg - Occ (hr) | Mean Temp (F) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 449 | 669 | 584 | 4859 | 981 | 1218 | 0 | 0 | 0 | 0 | 0 | 0 | 71.3 (F) |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 70 | 681 | 3935 | 1788 | 2286 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 1 | 151 | 738 | 4154 | 1668 | 2048 | 0 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1 | 1 | 0 | 0 | 1072 | 487 | 391 | 5049 | 788 | 973 | 0 | 0 | 0 | 0 | 0 | 0 | 70.8 (F) |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 3196 | 548 | 422 | 4336 | 122 | 136 | 0 | 0 | 0 | 0 | 0 | 0 | 68.7 (F) |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 3090 | 823 | 262 | 4358 | 114 | 113 | 0 | 0 | 0 | 0 | 0 | 0 | 68.7 (F) |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 3159 | 774 | 245 | 4356 | 115 | 111 | 0 | 0 | 0 | 0 | 0 | 0 | 68.7 (F) |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 3609 | 515 | 63 | 4334 | 98 | 141 | 0 | 0 | 0 | 0 | 0 | 0 | 68.5 (F) |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 1217 | 744 | 383 | 5006 | 601 | 809 | 0 | 0 | 0 | 0 | 0 | 0 | 70.5 (F) |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 127 | 112 | 0 | 7 | 373 | 418 | 525 | 3264 | 2196 | 1768 | 203 | 6 | 0 | 0 | 1 | 1 | 72.0 (F) |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 330 | 545 | 780 | 5674 | 770 | 656 | 5 | 0 | 0 | 0 | 0 | 0 | 71.2 (F) |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 2 | 2 | 0 | 0 | 775 | 854 | 957 | 2199 | 1696 | 2134 | 145 | 0 | 0 | 0 | 0 | 0 | 71.4 (F) |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 1208 | 296 | 529 | 5450 | 511 | 766 | 0 | 0 | 0 | 0 | 0 | 0 | 70.7 (F) |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 1203 | 343 | 495 | 5500 | 487 | 732 | 0 | 0 | 0 | 0 | 0 | 0 | 70.6 (F) |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 1245 | 343 | 480 | 5511 | 467 | 714 | 0 | 0 | 0 | 0 | 0 | 0 | 70.6 (F) |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 1547 | 398 | 272 | 5444 | 406 | 693 | 0 | 0 | 0 | 0 | 0 | 0 | 70.4 (F) |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 1700 | 1102 | 947 | 2987 | 920 | 1048 | 56 | 0 | 0 | 0 | 0 | 0 | 69.9 (F) |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 1414 | 1303 | 991 | 3188 | 899 | 926 | 39 | 0 | 0 | 0 | 0 | 0 | 70.0 (F) |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 1783 | 1135 | 919 | 3198 | 792 | 888 | 45 | 0 | 0 | 0 | 0 | 0 | 69.8 (F) |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2972 | 710 | 734 | 2958 | 533 | 770 | 77 | 6 | 0 | 0 | 0 | 0 | 69.0 (F) |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 32 | 303 | 595 | 3895 | 1573 | 2362 | 0 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 34 | 309 | 603 | 3947 | 1474 | 2393 | 0 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 85 | 448 | 723 | 4267 | 1367 | 1870 | 0 | 0 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 30 | 285 | 559 | 3227 | 1852 | 2807 | 0 | 0 | 0 | 0 | 0 | 0 | 72.5 (F) |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 18 | 251 | 542 | 3025 | 1854 | 3070 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 485 | 422 | 502 | 4447 | 1215 | 1689 | 0 | 0 | 0 | 0 | 0 | 0 | 71.6 (F) |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 21 | 255 | 510 | 3443 | 1691 | 2840 | 0 | 0 | 0 | 0 | 0 | 0 | 72.5 (F) |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 38 | 291 | 568 | 3756 | 1499 | 2608 | 0 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 25 | 280 | 553 | 3736 | 1537 | 2629 | 0 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 40 | 361 | 712 | 4207 | 1426 | 2014 | 0 | 0 | 0 | 0 | 0 | 0 | 72.0 (F) |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 12 | 182 | 548 | 3131 | 1811 | 3076 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 20 | 206 | 505 | 2996 | 1742 | 3291 | 0 | 0 | 0 | 0 | 0 | 0 | 72.7 (F) |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 17 | 273 | 629 | 3409 | 1858 | 2574 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 16 | 190 | 442 | 2714 | 1671 | 3727 | 0 | 0 | 0 | 0 | 0 | 0 | 72.9 (F) |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 18 | 233 | 510 | 2972 | 1723 | 3304 | 0 | 0 | 0 | 0 | 0 | 0 | 72.7 (F) |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 634 | 467 | 488 | 4778 | 1060 | 1333 | 0 | 0 | 0 | 0 | 0 | 0 | 71.3 (F) |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 76 | 362 | 539 | 3901 | 1471 | 2411 | 0 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 88 | 388 | 548 | 3968 | 1382 | 2386 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 76 | 367 | 555 | 3981 | 1426 | 2355 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 93 | 434 | 725 | 4367 | 1364 | 1777 | 0 | 0 | 0 | 0 | 0 | 0 | 71.8 (F) |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 31 | 279 | 569 | 3443 | 1762 | 2676 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 42 | 263 | 509 | 3150 | 1644 | 3152 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 31 | 286 | 627 | 3510 | 1884 | 2422 | 0 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 39 | 256 | 491 | 3058 | 1659 | 3257 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 36 | 294 | 569 | 3417 | 1703 | 2741 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 14 | 14 | 0 | 0 | 1310 | 433 | 360 | 5260 | 602 | 795 | 0 | 0 | 0 | 0 | 0 | 0 | 70.5 (F) |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 15 | 15 | 0 | 0 | 1124 | 427 | 370 | 4944 | 772 | 1123 | 0 | 0 | 0 | 0 | 0 | 0 | 70.8 (F) |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 11 | 11 | 0 | 0 | 1129 | 428 | 359 | 4914 | 776 | 1154 | 0 | 0 | 0 | 0 | 0 | 0 | 70.8 (F) |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 15 | 15 | 0 | 0 | 1123 | 435 | 368 | 4944 | 770 | 1120 | 0 | 0 | 0 | 0 | 0 | 0 | 70.8 (F) |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 2 | 2 | 0 | 0 | 1157 | 483 | 361 | 5114 | 670 | 975 | 0 | 0 | 0 | 0 | 0 | 0 | 70.7 (F) |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1 | 1 | 0 | 0 | 1041 | 463 | 397 | 4689 | 886 | 1284 | 0 | 0 | 0 | 0 | 0 | 0 | 70.9 (F) |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 6 | 6 | 0 | 0 | 1057 | 440 | 373 | 4548 | 877 | 1465 | 0 | 0 | 0 | 0 | 0 | 0 | 71.0 (F) |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1 | 1 | 0 | 0 | 1060 | 483 | 425 | 4728 | 890 | 1174 | 0 | 0 | 0 | 0 | 0 | 0 | 70.9 (F) |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 6 | 6 | 0 | 0 | 1053 | 435 | 373 | 4545 | 880 | 1474 | 0 | 0 | 0 | 0 | 0 | 0 | 71.0 (F) |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1 | 1 | 0 | 0 | 1060 | 457 | 383 | 4690 | 833 | 1337 | 0 | 0 | 0 | 0 | 0 | 0 | 70.9 (F) |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2665 | 944 | 667 | 2874 | 705 | 843 | 54 | 8 | 0 | 0 | 0 | 0 | 69.2 (F) |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 444 | 687 | 588 | 4958 | 891 | 1192 | 0 | 0 | 0 | 0 | 0 | 0 | 71.3 (F) |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 796 | 611 | 448 | 5087 | 724 | 1094 | 0 | 0 | 0 | 0 | 0 | 0 | 71.0 (F) |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 818 | 527 | 464 | 5418 | 803 | 730 | 0 | 0 | 0 | 0 | 0 | 0 | 70.9 (F) |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 796 | 493 | 495 | 5447 | 800 | 729 | 0 | 0 | 0 | 0 | 0 | 0 | 70.9 (F) |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 872 | 530 | 474 | 5554 | 729 | 601 | 0 | 0 | 0 | 0 | 0 | 0 | 70.8 (F) |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 14 | 14 | 0 | 0 | 1481 | 408 | 348 | 5616 | 497 | 410 | 0 | 0 | 0 | 0 | 0 | 0 | 70.3 (F) |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 3123 | 568 | 692 | 3104 | 484 | 731 | 58 | 0 | 0 | 0 | 0 | 0 | 68.9 (F) |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 3177 | 578 | 670 | 3115 | 472 | 695 | 53 | 0 | 0 | 0 | 0 | 0 | 68.9 (F) |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 3279 | 590 | 631 | 3088 | 442 | 668 | 62 | 0 | 0 | 0 | 0 | 0 | 68.8 (F) |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 3793 | 588 | 336 | 2978 | 366 | 610 | 67 | 22 | 0 | 0 | 0 | 0 | 68.5 (F) |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 277 | 645 | 710 | 4948 | 909 | 1271 | 0 | 0 | 0 | 0 | 0 | 0 | 71.5 (F) |
| Zone | < 30 (%) | 30-35 (%) | 35-40 (%) | 40-45 (%) | 45-50 (%) | 50-55 (%) | 55-60 (%) | 60-65 (%) | 65-70 (%) | 70-75 (%) | 75-80 (%) | >= 80 (%) | Mean Relative Humidity (%) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 6919 | 646 | 649 | 363 | 140 | 32 | 11 | 0 | 0 | 0 | 0 | 0 | 17.4 (%) |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 7108 | 681 | 508 | 293 | 125 | 29 | 16 | 0 | 0 | 0 | 0 | 0 | 16.8 (%) |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 7074 | 677 | 527 | 299 | 135 | 31 | 17 | 0 | 0 | 0 | 0 | 0 | 16.9 (%) |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 6917 | 633 | 577 | 356 | 193 | 56 | 22 | 6 | 0 | 0 | 0 | 0 | 17.1 (%) |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 6550 | 617 | 477 | 426 | 299 | 217 | 100 | 44 | 21 | 9 | 0 | 0 | 18.6 (%) |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 6586 | 587 | 472 | 419 | 296 | 216 | 107 | 44 | 24 | 8 | 1 | 0 | 18.6 (%) |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 6577 | 591 | 474 | 419 | 294 | 220 | 107 | 45 | 24 | 8 | 1 | 0 | 18.6 (%) |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 6506 | 620 | 471 | 400 | 299 | 255 | 106 | 58 | 35 | 8 | 2 | 0 | 18.8 (%) |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 5907 | 767 | 701 | 664 | 408 | 217 | 73 | 15 | 8 | 0 | 0 | 0 | 23.1 (%) |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 3103 | 815 | 886 | 1077 | 1060 | 829 | 557 | 255 | 107 | 42 | 26 | 3 | 37.1 (%) |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 5827 | 830 | 619 | 609 | 500 | 228 | 115 | 32 | 0 | 0 | 0 | 0 | 24.1 (%) |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 6506 | 823 | 663 | 522 | 205 | 41 | 0 | 0 | 0 | 0 | 0 | 0 | 20.5 (%) |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 6911 | 651 | 612 | 371 | 153 | 44 | 9 | 9 | 0 | 0 | 0 | 0 | 16.8 (%) |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 6908 | 640 | 621 | 365 | 156 | 49 | 9 | 12 | 0 | 0 | 0 | 0 | 16.8 (%) |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 6898 | 648 | 604 | 387 | 154 | 50 | 10 | 9 | 0 | 0 | 0 | 0 | 16.8 (%) |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 6841 | 656 | 597 | 436 | 162 | 49 | 17 | 2 | 0 | 0 | 0 | 0 | 16.9 (%) |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 6696 | 733 | 661 | 414 | 188 | 50 | 6 | 5 | 7 | 0 | 0 | 0 | 18.8 (%) |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 6670 | 735 | 647 | 390 | 220 | 76 | 11 | 3 | 8 | 0 | 0 | 0 | 18.8 (%) |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 6639 | 740 | 666 | 401 | 213 | 79 | 11 | 3 | 8 | 0 | 0 | 0 | 18.9 (%) |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 6649 | 703 | 695 | 455 | 176 | 62 | 10 | 7 | 3 | 0 | 0 | 0 | 18.4 (%) |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 3218 | 1352 | 1080 | 1157 | 990 | 619 | 249 | 70 | 23 | 2 | 0 | 0 | 35.5 (%) |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 3209 | 1356 | 1083 | 1153 | 987 | 623 | 250 | 74 | 23 | 2 | 0 | 0 | 35.6 (%) |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 3149 | 1341 | 1037 | 1067 | 1040 | 697 | 301 | 103 | 23 | 2 | 0 | 0 | 36.0 (%) |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 3303 | 1333 | 1131 | 1188 | 948 | 556 | 217 | 64 | 19 | 1 | 0 | 0 | 35.2 (%) |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 3328 | 1363 | 1137 | 1224 | 910 | 523 | 204 | 53 | 18 | 0 | 0 | 0 | 35.0 (%) |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 4429 | 962 | 932 | 1005 | 739 | 458 | 181 | 42 | 12 | 0 | 0 | 0 | 31.6 (%) |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3704 | 1274 | 1170 | 1146 | 812 | 437 | 173 | 33 | 11 | 0 | 0 | 0 | 33.8 (%) |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3680 | 1232 | 1125 | 1148 | 871 | 465 | 180 | 40 | 17 | 2 | 0 | 0 | 34.0 (%) |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3683 | 1238 | 1122 | 1146 | 849 | 470 | 184 | 45 | 21 | 2 | 0 | 0 | 34.0 (%) |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3631 | 1173 | 1067 | 1139 | 905 | 562 | 207 | 54 | 20 | 2 | 0 | 0 | 34.4 (%) |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3752 | 1264 | 1146 | 1163 | 783 | 444 | 159 | 35 | 14 | 0 | 0 | 0 | 33.6 (%) |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3777 | 1267 | 1188 | 1147 | 736 | 442 | 152 | 37 | 14 | 0 | 0 | 0 | 33.5 (%) |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3705 | 1213 | 1082 | 1155 | 817 | 506 | 189 | 75 | 18 | 0 | 0 | 0 | 34.1 (%) |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3844 | 1295 | 1260 | 1093 | 680 | 411 | 137 | 31 | 9 | 0 | 0 | 0 | 33.2 (%) |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3774 | 1283 | 1199 | 1151 | 745 | 434 | 135 | 31 | 8 | 0 | 0 | 0 | 33.5 (%) |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 4477 | 922 | 877 | 942 | 747 | 518 | 197 | 57 | 21 | 2 | 0 | 0 | 31.6 (%) |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3727 | 1200 | 1090 | 1132 | 868 | 493 | 183 | 45 | 20 | 2 | 0 | 0 | 34.0 (%) |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3717 | 1187 | 1107 | 1132 | 872 | 496 | 182 | 49 | 17 | 1 | 0 | 0 | 34.0 (%) |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3720 | 1184 | 1093 | 1136 | 857 | 508 | 193 | 47 | 20 | 2 | 0 | 0 | 34.0 (%) |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3668 | 1154 | 1021 | 1093 | 937 | 578 | 228 | 58 | 21 | 2 | 0 | 0 | 34.4 (%) |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3779 | 1211 | 1107 | 1159 | 815 | 466 | 172 | 38 | 13 | 0 | 0 | 0 | 33.7 (%) |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3819 | 1253 | 1194 | 1133 | 725 | 439 | 151 | 34 | 12 | 0 | 0 | 0 | 33.4 (%) |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3760 | 1186 | 1080 | 1124 | 808 | 504 | 201 | 77 | 20 | 0 | 0 | 0 | 34.0 (%) |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3835 | 1261 | 1221 | 1116 | 716 | 421 | 146 | 34 | 10 | 0 | 0 | 0 | 33.3 (%) |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3772 | 1231 | 1133 | 1160 | 808 | 454 | 158 | 33 | 11 | 0 | 0 | 0 | 33.6 (%) |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 4975 | 789 | 807 | 817 | 639 | 442 | 199 | 70 | 19 | 3 | 0 | 0 | 29.0 (%) |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 4666 | 863 | 870 | 890 | 695 | 486 | 200 | 69 | 18 | 3 | 0 | 0 | 30.6 (%) |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 4666 | 867 | 877 | 890 | 696 | 477 | 200 | 68 | 16 | 3 | 0 | 0 | 30.6 (%) |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 4667 | 860 | 869 | 889 | 696 | 488 | 201 | 69 | 18 | 3 | 0 | 0 | 30.6 (%) |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 4653 | 844 | 838 | 879 | 717 | 524 | 214 | 69 | 19 | 3 | 0 | 0 | 30.7 (%) |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 4696 | 883 | 893 | 885 | 669 | 467 | 188 | 59 | 17 | 3 | 0 | 0 | 30.4 (%) |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 4705 | 900 | 910 | 894 | 656 | 444 | 177 | 57 | 14 | 3 | 0 | 0 | 30.3 (%) |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 4692 | 878 | 881 | 858 | 655 | 478 | 213 | 75 | 27 | 3 | 0 | 0 | 30.5 (%) |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 4706 | 901 | 910 | 894 | 656 | 443 | 176 | 57 | 14 | 3 | 0 | 0 | 30.3 (%) |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 4692 | 891 | 899 | 887 | 674 | 467 | 175 | 59 | 14 | 2 | 0 | 0 | 30.4 (%) |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 6562 | 734 | 686 | 479 | 201 | 78 | 9 | 5 | 6 | 0 | 0 | 0 | 19.3 (%) |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 7038 | 666 | 585 | 313 | 121 | 30 | 7 | 0 | 0 | 0 | 0 | 0 | 16.5 (%) |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 6981 | 671 | 619 | 335 | 115 | 30 | 9 | 0 | 0 | 0 | 0 | 0 | 16.7 (%) |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 6978 | 631 | 556 | 312 | 186 | 70 | 13 | 11 | 3 | 0 | 0 | 0 | 16.7 (%) |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 6973 | 637 | 549 | 316 | 183 | 74 | 11 | 11 | 6 | 0 | 0 | 0 | 16.7 (%) |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 6943 | 636 | 545 | 341 | 184 | 82 | 11 | 10 | 8 | 0 | 0 | 0 | 16.8 (%) |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 6850 | 611 | 545 | 379 | 228 | 95 | 31 | 12 | 9 | 0 | 0 | 0 | 17.1 (%) |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 6561 | 778 | 684 | 435 | 201 | 74 | 16 | 5 | 6 | 0 | 0 | 0 | 18.6 (%) |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 6552 | 759 | 703 | 438 | 203 | 78 | 15 | 5 | 7 | 0 | 0 | 0 | 18.7 (%) |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 6535 | 769 | 692 | 457 | 202 | 78 | 15 | 7 | 5 | 0 | 0 | 0 | 18.7 (%) |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 6414 | 798 | 708 | 525 | 217 | 74 | 14 | 10 | 0 | 0 | 0 | 0 | 18.6 (%) |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 6303 | 804 | 697 | 590 | 280 | 66 | 20 | 0 | 0 | 0 | 0 | 0 | 20.6 (%) |
Zone Overview
| Area (ft^2) | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume (ft^3) | Multiplier | Above Ground Gross Wall Area (ft^2) | Underground Gross Wall Area (ft^2) | Window Glass Area (ft^2) | Lighting (W/ft^2) | People (ft^2/person) | Plug and Process (W/ft^2) | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1620.08 | Yes | Yes | 17820.49 | 1.00 | 351.98 | 0.0 | 105.7 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1781.98 | 1.00 | 65.98 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.79 | 107.64 | 0.09 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.91 | 53.82 | 0.09 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1755.16 | Yes | Yes | 19306.53 | 1.00 | 1012.02 | 0.0 | 159.63 | 1.06 | 107.64 | 0.23 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 15444.16 | 1.00 | 571.99 | 0.0 | 70.83 | 1.11 | 215.06 | 0.7 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 2375.97 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1484.98 | 1.00 | 55.0 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 1053.03 | Yes | Yes | 11582.86 | 1.00 | 429.05 | 0.0 | 53.17 | 0.57 | 1075.31 | 0.09 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 1.24 | 2173.88 | 0.09 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 864.02 | Yes | Yes | 9504.59 | 1.00 | 351.98 | 0.0 | 53.17 | 1.24 | 2173.88 | 0.09 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 0.88 | 322.59 | 0.09 |
| Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.77 | 287.83 | 0.19 | |||
| Conditioned Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.77 | 287.83 | 0.19 | |||
| Unconditioned Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | |||
| Not Part of Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| Heating/Cooling | Calculated Design Load | Design Load With Sizing Factor | Calculated Design Air Flow (ft^3/min) | Design Air Flow With Sizing Factor (ft^3/min) | Date/Time Of Peak | Outdoor Temperature at Peak Load (F) | Outdoor Humidity Ratio at Peak Load (lbWater/lbAir) | |
|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.44 (ton) | 0.48 (ton) | 243.67 | 266.98 | 7/21 16:45:00 | 76.12 | 0.01 |
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 10.39 (kBtu/h) | 13.5 (kBtu/h) | 245.79 | 319.95 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.32 (ton) | 0.35 (ton) | 175.87 | 192.82 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 6.18 (kBtu/h) | 8.03 (kBtu/h) | 146.2 | 190.7 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.32 (ton) | 0.35 (ton) | 175.87 | 192.82 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 7.49 (kBtu/h) | 9.74 (kBtu/h) | 177.99 | 230.96 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.43 (ton) | 0.47 (ton) | 235.2 | 258.5 | 7/21 15:00:00 | 78.26 | 0.01 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 21.06 (kBtu/h) | 27.37 (kBtu/h) | 504.29 | 654.73 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.07 (ton) | 0.07 (ton) | 36.02 | 131.37 | 7/21 17:00:00 | 75.76 | 0.01 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | Heating | 1.42 (kBtu/h) | 1.85 (kBtu/h) | 33.9 | 131.37 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 131.37 | 7/21 17:00:00 | 75.76 | 0.01 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | Heating | 1.0 (kBtu/h) | 1.3 (kBtu/h) | 23.31 | 131.37 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 131.37 | 7/21 17:00:00 | 75.76 | 0.01 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | Heating | 1.2 (kBtu/h) | 1.56 (kBtu/h) | 27.55 | 131.37 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 42.38 | 131.37 | 7/21 14:30:00 | 78.26 | 0.01 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | Heating | 2.9 (kBtu/h) | 3.77 (kBtu/h) | 69.92 | 131.37 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | Cooling | 0.22 (ton) | 0.24 (ton) | 120.78 | 133.49 | 7/21 13:15:00 | 77.59 | 0.01 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | Heating | 2.04 (kBtu/h) | 2.65 (kBtu/h) | 48.73 | 65.69 | 1/21 10:00:00 | -36.58 | 0.0 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | Cooling | 0.27 (ton) | 0.3 (ton) | 150.44 | 300.88 | 7/21 13:00:00 | 77.36 | 0.01 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | Heating | 1.64 (kBtu/h) | 2.14 (kBtu/h) | 38.14 | 300.88 | 1/21 10:00:00 | -36.58 | 0.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | Cooling | 0.84 (ton) | 0.93 (ton) | 468.27 | 514.89 | 7/21 15:00:00 | 78.26 | 0.01 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | Heating | 5.73 (kBtu/h) | 7.44 (kBtu/h) | 133.49 | 500.06 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | Cooling | 0.89 (ton) | 0.98 (ton) | 493.7 | 544.55 | 7/21 13:30:00 | 77.81 | 0.01 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | Heating | 6.65 (kBtu/h) | 8.65 (kBtu/h) | 156.8 | 203.41 | 1/21 08:00:00 | -36.58 | 0.0 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | Cooling | 0.03 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | Heating | 3.95 (kBtu/h) | 5.13 (kBtu/h) | 95.35 | 122.9 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | Cooling | 0.03 (ton) | 0.04 (ton) | 19.07 | 19.07 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | Heating | 3.56 (kBtu/h) | 4.63 (kBtu/h) | 84.76 | 110.18 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | Cooling | 0.03 (ton) | 0.04 (ton) | 16.95 | 19.07 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | Heating | 3.87 (kBtu/h) | 5.04 (kBtu/h) | 93.23 | 120.78 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 25.43 | 27.55 | 7/21 14:45:00 | 78.26 | 0.01 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | Heating | 5.91 (kBtu/h) | 7.68 (kBtu/h) | 141.96 | 184.34 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 25.43 | 29.66 | 7/21 14:00:00 | 78.26 | 0.01 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Heating | 1.43 (kBtu/h) | 1.87 (kBtu/h) | 33.9 | 44.5 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.04 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 14:00:00 | 78.26 | 0.01 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | Heating | 1.21 (kBtu/h) | 1.57 (kBtu/h) | 29.66 | 38.14 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.03 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 16:00:00 | 77.2 | 0.01 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | Heating | 1.37 (kBtu/h) | 1.78 (kBtu/h) | 31.78 | 42.38 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 27.55 | 29.66 | 7/21 14:00:00 | 78.26 | 0.01 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | Heating | 2.72 (kBtu/h) | 3.54 (kBtu/h) | 65.69 | 84.76 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 52.97 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 2.13 (kBtu/h) | 2.77 (kBtu/h) | 50.85 | 65.69 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.09 (ton) | 46.62 | 52.97 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 2.22 (kBtu/h) | 2.89 (kBtu/h) | 52.97 | 67.8 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 46.62 | 50.85 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 2.56 (kBtu/h) | 3.33 (kBtu/h) | 61.45 | 78.4 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 67.8 | 74.16 | 7/21 13:30:00 | 77.81 | 0.01 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Heating | 2.39 (kBtu/h) | 3.11 (kBtu/h) | 57.21 | 74.16 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.14 (ton) | 0.15 (ton) | 76.28 | 84.76 | 7/21 13:30:00 | 77.81 | 0.01 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Heating | 2.33 (kBtu/h) | 3.03 (kBtu/h) | 55.09 | 72.04 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 59.33 | 63.57 | 7/21 21:00:00 | 67.75 | 0.01 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | Heating | 3.93 (kBtu/h) | 5.11 (kBtu/h) | 93.23 | 122.9 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.39 (ton) | 0.42 (ton) | 214.01 | 235.2 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 6.29 (kBtu/h) | 8.18 (kBtu/h) | 148.32 | 192.82 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.28 (ton) | 0.31 (ton) | 154.68 | 169.51 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 5.46 (kBtu/h) | 7.1 (kBtu/h) | 129.25 | 167.39 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.33 (ton) | 0.36 (ton) | 182.22 | 199.17 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 6.48 (kBtu/h) | 8.42 (kBtu/h) | 152.56 | 199.17 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 52.97 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 2.14 (kBtu/h) | 2.79 (kBtu/h) | 50.85 | 65.69 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 61.45 | 67.8 | 7/21 13:45:00 | 78.04 | 0.01 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 2.0 (kBtu/h) | 2.59 (kBtu/h) | 46.62 | 61.45 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.43 (ton) | 0.47 (ton) | 237.31 | 260.62 | 7/21 13:45:00 | 78.04 | 0.01 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 6.63 (kBtu/h) | 8.62 (kBtu/h) | 156.8 | 203.41 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 65.69 | 72.04 | 7/21 13:45:00 | 78.04 | 0.01 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.94 (kBtu/h) | 2.53 (kBtu/h) | 46.62 | 59.33 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.45 (ton) | 0.49 (ton) | 247.91 | 273.34 | 7/21 13:45:00 | 78.04 | 0.01 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 6.38 (kBtu/h) | 8.3 (kBtu/h) | 150.44 | 197.06 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.13 (ton) | 0.14 (ton) | 69.92 | 76.28 | 7/21 13:45:00 | 78.04 | 0.01 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.91 (kBtu/h) | 2.48 (kBtu/h) | 44.5 | 59.33 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 52.97 | 57.21 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | Heating | 4.63 (kBtu/h) | 6.01 (kBtu/h) | 110.18 | 144.08 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.36 (ton) | 0.39 (ton) | 197.06 | 218.24 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 7.96 (kBtu/h) | 10.35 (kBtu/h) | 188.58 | 245.79 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.29 (ton) | 0.32 (ton) | 161.03 | 175.87 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 6.83 (kBtu/h) | 8.88 (kBtu/h) | 163.15 | 211.89 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.35 (ton) | 0.38 (ton) | 190.7 | 209.77 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 7.95 (kBtu/h) | 10.33 (kBtu/h) | 188.58 | 245.79 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 55.09 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 2.52 (kBtu/h) | 3.28 (kBtu/h) | 59.33 | 78.4 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 63.57 | 69.92 | 7/21 13:45:00 | 78.04 | 0.01 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 2.37 (kBtu/h) | 3.08 (kBtu/h) | 57.21 | 74.16 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.45 (ton) | 0.49 (ton) | 245.79 | 271.22 | 7/21 13:45:00 | 78.04 | 0.01 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 7.88 (kBtu/h) | 10.24 (kBtu/h) | 186.46 | 243.67 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 65.69 | 72.04 | 7/21 13:45:00 | 78.04 | 0.01 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 2.2 (kBtu/h) | 2.86 (kBtu/h) | 52.97 | 67.8 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.44 (ton) | 0.49 (ton) | 245.79 | 269.1 | 7/21 13:45:00 | 78.04 | 0.01 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 7.73 (kBtu/h) | 10.05 (kBtu/h) | 184.34 | 239.43 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 65.69 | 72.04 | 7/21 13:45:00 | 78.04 | 0.01 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 2.27 (kBtu/h) | 2.95 (kBtu/h) | 52.97 | 69.92 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 55.09 | 61.45 | 7/21 14:15:00 | 78.26 | 0.01 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | Heating | 7.8 (kBtu/h) | 10.14 (kBtu/h) | 186.46 | 243.67 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.34 (ton) | 0.37 (ton) | 188.58 | 207.65 | 7/21 14:00:00 | 78.26 | 0.01 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 19.9 (kBtu/h) | 25.87 (kBtu/h) | 476.75 | 618.71 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.29 (ton) | 0.32 (ton) | 161.03 | 177.99 | 7/21 14:00:00 | 78.26 | 0.01 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 16.48 (kBtu/h) | 21.42 (kBtu/h) | 394.11 | 512.77 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.34 (ton) | 0.37 (ton) | 186.46 | 205.53 | 7/21 14:00:00 | 78.26 | 0.01 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 19.84 (kBtu/h) | 25.79 (kBtu/h) | 474.63 | 616.59 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 52.97 | 7/21 14:15:00 | 78.26 | 0.01 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 5.67 (kBtu/h) | 7.37 (kBtu/h) | 135.61 | 175.87 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.17 (ton) | 0.18 (ton) | 93.23 | 101.71 | 7/21 13:30:00 | 77.81 | 0.01 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 5.59 (kBtu/h) | 7.27 (kBtu/h) | 133.49 | 173.75 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.66 (ton) | 0.73 (ton) | 366.57 | 402.59 | 7/21 13:30:00 | 77.81 | 0.01 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 19.75 (kBtu/h) | 25.67 (kBtu/h) | 472.51 | 614.48 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.17 (ton) | 0.19 (ton) | 93.23 | 103.83 | 7/21 13:30:00 | 77.81 | 0.01 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 5.48 (kBtu/h) | 7.12 (kBtu/h) | 131.37 | 169.51 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.65 (ton) | 0.72 (ton) | 360.21 | 396.23 | 7/21 13:15:00 | 77.59 | 0.01 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 19.7 (kBtu/h) | 25.6 (kBtu/h) | 470.39 | 612.36 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.17 (ton) | 0.18 (ton) | 93.23 | 101.71 | 7/21 13:30:00 | 77.81 | 0.01 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 5.52 (kBtu/h) | 7.17 (kBtu/h) | 131.37 | 171.63 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.43 (ton) | 0.47 (ton) | 237.31 | 260.62 | 7/21 13:30:00 | 77.81 | 0.01 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Heating | 7.59 (kBtu/h) | 9.86 (kBtu/h) | 180.1 | 235.2 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 55.09 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.89 (kBtu/h) | 2.46 (kBtu/h) | 44.5 | 57.21 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.21 (ton) | 0.23 (ton) | 114.42 | 125.01 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 4.93 (kBtu/h) | 6.4 (kBtu/h) | 116.54 | 152.56 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | Cooling | 0.04 (ton) | 0.04 (ton) | 21.19 | 23.31 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | Heating | 3.88 (kBtu/h) | 5.04 (kBtu/h) | 93.23 | 120.78 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | Cooling | 0.04 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | Heating | 3.49 (kBtu/h) | 4.54 (kBtu/h) | 82.64 | 108.06 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | Cooling | 0.04 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | Heating | 3.81 (kBtu/h) | 4.96 (kBtu/h) | 91.11 | 118.66 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 29.66 | 31.78 | 7/21 14:30:00 | 78.26 | 0.01 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | Heating | 5.89 (kBtu/h) | 7.65 (kBtu/h) | 141.96 | 184.34 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 23.31 | 25.43 | 7/21 16:00:00 | 77.2 | 0.01 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | Heating | 4.22 (kBtu/h) | 5.49 (kBtu/h) | 101.71 | 131.37 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 23.31 | 25.43 | 7/21 16:00:00 | 77.2 | 0.01 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | Heating | 3.88 (kBtu/h) | 5.04 (kBtu/h) | 93.23 | 120.78 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 23.31 | 25.43 | 7/21 16:00:00 | 77.2 | 0.01 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | Heating | 4.21 (kBtu/h) | 5.48 (kBtu/h) | 101.71 | 131.37 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 36.02 | 40.26 | 7/21 14:15:00 | 78.26 | 0.01 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | Heating | 6.07 (kBtu/h) | 7.88 (kBtu/h) | 146.2 | 188.58 | 1/21 09:00:00 | -36.58 | 0.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 50.85 | 57.21 | 7/21 22:00:00 | 66.15 | 0.01 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.75 (kBtu/h) | 2.28 (kBtu/h) | 42.38 | 52.97 | 1/21 09:00:00 | -36.58 | 0.0 |
Zone Equipment Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
Air Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.35 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 68.0 to 68.0 | F | |||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 32,185 | ft^2 | 42 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 42 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Make-up air unit Occ Sch | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | DifferentialEnthalpy | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-CorridorFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,620 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr1 Sys-3 Flr-2 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr2 Sys-3 Flr-1 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr3 Sys-3 Flr-4 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr4 Sys-3 Flr-3 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-EmployeeLoungeFlr1 Sys-3 Flr-2 Sch-B HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontLoungeFlr1 Sys-3 Flr-2 Sch-H HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr1 Sys-4 Flr-2 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr2 Sys-4 Flr-1 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr3 Sys-4 Flr-4 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr4 Sys-4 Flr-3 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr1 Sys-4 Flr-2 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr2 Sys-4 Flr-1 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr3 Sys-4 Flr-4 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr4 Sys-4 Flr-3 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-LaundryRoomFlr1 Sys-4 Flr-2 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,053 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-MechanicalRoomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-MeetingRoomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 864 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr1 Sys-4 Flr-2 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr2 Sys-4 Flr-1 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr3 Sys-4 Flr-4 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr4 Sys-4 Flr-3 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RestroomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:Water | Autosized | gal/min | Plant Loop | Chilled Water Loop | ||
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:VariableVolume | Autosized | cfm | Pressure Rise | 5.85 | inH_{2}O | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 55.4 to 55.4 | F | |||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 2 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:VAV:Reheat | 2 | ||||
(controls) |
||||||
| HVAC Operation Schedule | VAV with Reheat Occ Sch | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
Plant Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:Chiller:Electric:EIR | 24,418.18 | Btu/h | Reference COP | 4.50 | ||
| OS:Chiller:Electric:EIR (cont) | Chiller Source | Condenser Water Loop | ||||
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 44.6 to 44.6 | F | |||
| OS:Chiller:Electric:EIR | 0.00 | Btu/h | Reference COP | 4.50 | ||
| OS:Chiller:Electric:EIR (cont) | Chiller Source | Condenser Water Loop | ||||
(demand) |
||||||
| OS:Coil:Cooling:Water | Air Loop | VAV with Reheat | ||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 44.60 | F | ||||
| Loop Design Temperature Difference | 10.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:CoolingTower:SingleSpeed - Air | Autosized | gal/min | ||||
| OS:CoolingTower:SingleSpeed (cont) - Water | Autosized | cfm | Fan Power at Design Air Flow Rate | 277,957.18 | W | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 84.2 to 84.2 | F | |||
(demand) |
||||||
| OS:Chiller:Electric:EIR | Plant Loop | Chilled Water Loop | ||||
| OS:Chiller:Electric:EIR | Plant Loop | Chilled Water Loop | ||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 84.20 | F | ||||
| Loop Design Temperature Difference | 10.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:WaterHeater:Mixed | 300 | gal | Heater Thermal Efficiency | 1.00 | fraction | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 140.0 to 140.0 | F | |||
(demand) |
||||||
| OS:WaterUse:Connections | Water Use Connections 1 | |||||
| OS:WaterUse:Connections | Water Use Connections 2 | |||||
| OS:WaterUse:Connections | Water Use Connections 3 | |||||
| OS:WaterUse:Connections | Water Use Connections 4 | |||||
| OS:WaterUse:Connections | Water Use Connections 5 | |||||
| OS:WaterUse:Connections | Water Use Connections 6 | |||||
| OS:WaterUse:Connections | Water Use Connections 7 | |||||
| OS:WaterUse:Connections | Water Use Connections 8 | |||||
| OS:WaterUse:Connections | Water Use Connections 9 | |||||
| OS:WaterUse:Connections | Water Use Connections 10 | |||||
| OS:WaterUse:Connections | Water Use Connections 11 | |||||
| OS:WaterUse:Connections | Water Use Connections 12 | |||||
| OS:WaterUse:Connections | Water Use Connections 13 | |||||
| OS:WaterUse:Connections | Water Use Connections 14 | |||||
| OS:WaterUse:Connections | Water Use Connections 15 | |||||
| OS:WaterUse:Connections | Water Use Connections 16 | |||||
| OS:WaterUse:Connections | Water Use Connections 17 | |||||
| OS:WaterUse:Connections | Water Use Connections 18 | |||||
| OS:WaterUse:Connections | Water Use Connections 19 | |||||
| OS:WaterUse:Connections | Water Use Connections 20 | |||||
| OS:WaterUse:Connections | Water Use Connections 21 | |||||
| OS:WaterUse:Connections | Water Use Connections 22 | |||||
| OS:WaterUse:Connections | Water Use Connections 23 | |||||
| OS:WaterUse:Connections | Water Use Connections 24 | |||||
| OS:WaterUse:Connections | Water Use Connections 25 | |||||
| OS:WaterUse:Connections | Water Use Connections 26 | |||||
| OS:WaterUse:Connections | Water Use Connections 27 | |||||
| OS:WaterUse:Connections | Water Use Connections 28 | |||||
| OS:WaterUse:Connections | Water Use Connections 29 | |||||
| OS:WaterUse:Connections | Water Use Connections 30 | |||||
| OS:WaterUse:Connections | Water Use Connections 31 | |||||
| OS:WaterUse:Connections | Water Use Connections 32 | |||||
| OS:WaterUse:Connections | Water Use Connections 33 | |||||
| OS:WaterUse:Connections | Water Use Connections 34 | |||||
| OS:WaterUse:Connections | Water Use Connections 35 | |||||
| OS:WaterUse:Connections | Water Use Connections 36 | |||||
| OS:WaterUse:Connections | Water Use Connections 37 | |||||
| OS:WaterUse:Connections | Water Use Connections 38 | |||||
| OS:WaterUse:Connections | Water Use Connections 39 | |||||
| OS:WaterUse:Connections | Water Use Connections 40 | |||||
| OS:WaterUse:Connections | Water Use Connections 41 | |||||
| OS:WaterUse:Connections | Water Use Connections 42 | |||||
| OS:WaterUse:Connections | Water Use Connections 43 | |||||
| OS:WaterUse:Connections | Water Use Connections 44 | |||||
| OS:WaterUse:Connections | Water Use Connections 45 | |||||
| OS:WaterUse:Connections | Water Use Connections 46 | |||||
| OS:WaterUse:Connections | Water Use Connections 47 | |||||
| OS:WaterUse:Connections | Water Use Connections 48 | |||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 50.0 to 140.0 | F | ||||
| Design Loop Exit Temperature | 140.00 | F | ||||
| Loop Design Temperature Difference | 9.00 | R |
Outdoor Air
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume (ft^3) | Avg. Mechanical Ventilation (ach) | Min. Mechanical Ventilation (ach) | Avg. Infiltration (ach) | Min. Infiltration (ach) | Avg. Simple Ventilation (ach) | Min. Simple Ventilation (ach) | |
|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.86 | 1.51 | 17820 | 0.331 | 0.318 | 0.042 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.418 | 0.391 | 0.043 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.414 | 0.391 | 0.048 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.406 | 0.388 | 0.4 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1782 | 4.467 | 4.344 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.459 | 5.309 | 0.102 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.459 | 5.309 | 0.113 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.459 | 5.309 | 0.483 | 0.0 | 0.0 | 0.0 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 1.56 | 3.26 | 3861 | 1.023 | 0.989 | 0.079 | 0.0 | 0.0 | 0.0 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 3.12 | 6.52 | 3861 | 1.197 | 0.0 | 0.079 | 0.0 | 0.0 | 0.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 14.67 | 16.31 | 19307 | 1.572 | 1.511 | 0.111 | 0.0 | 0.0 | 0.0 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 3.51 | 6.53 | 15444 | 0.717 | 0.0 | 0.08 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 2376 | 0.33 | 0.318 | 0.342 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.403 | 0.388 | 0.43 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.403 | 0.388 | 0.475 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.403 | 0.388 | 0.858 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1485 | 0.387 | 0.375 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.473 | 0.459 | 0.103 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.473 | 0.459 | 0.114 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.472 | 0.459 | 0.49 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.632 | 0.585 | 0.078 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.631 | 0.585 | 0.078 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.624 | 0.585 | 0.078 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3861 | 0.64 | 0.586 | 0.078 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3861 | 0.644 | 0.586 | 0.078 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.759 | 0.713 | 0.302 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.786 | 0.716 | 0.098 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.781 | 0.716 | 0.098 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.78 | 0.716 | 0.098 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.769 | 0.716 | 0.098 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.789 | 0.717 | 0.098 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.793 | 0.717 | 0.098 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.776 | 0.717 | 0.098 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.801 | 0.718 | 0.099 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.794 | 0.717 | 0.098 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.753 | 0.712 | 0.334 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.776 | 0.715 | 0.109 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.775 | 0.715 | 0.109 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.774 | 0.715 | 0.109 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.764 | 0.715 | 0.109 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.783 | 0.716 | 0.109 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.793 | 0.716 | 0.109 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.775 | 0.716 | 0.109 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.795 | 0.716 | 0.109 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.787 | 0.716 | 0.109 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.746 | 0.712 | 0.707 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.751 | 0.712 | 0.465 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.751 | 0.712 | 0.465 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.751 | 0.712 | 0.465 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.749 | 0.712 | 0.465 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.754 | 0.712 | 0.465 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.758 | 0.712 | 0.465 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.753 | 0.712 | 0.465 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.758 | 0.712 | 0.465 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.756 | 0.712 | 0.465 | 0.0 | 0.0 | 0.0 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.62 | 0.98 | 11583 | 0.387 | 0.375 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.09 | 0.16 | 3861 | 0.331 | 0.318 | 0.078 | 0.0 | 0.0 | 0.0 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.23 | 0.4 | 9505 | 0.33 | 0.318 | 0.078 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 2377 | 0.333 | 0.318 | 0.342 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.406 | 0.388 | 0.43 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.408 | 0.388 | 0.475 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.454 | 0.388 | 0.858 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 2377 | 0.387 | 0.376 | 0.36 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.472 | 0.459 | 0.452 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.472 | 0.459 | 0.5 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.472 | 0.459 | 0.903 | 0.0 | 0.0 | 0.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.62 | 1.09 | 3861 | 0.331 | 0.318 | 0.078 | 0.0 | 0.0 | 0.0 |
Cash Flow
No Data to Show for Cash Flow
Site and Source Summary
| Total Energy (kBtu) | Energy Per Total Building Area (kBtu/ft^2) | Energy Per Conditioned Building Area (kBtu/ft^2) | |
|---|---|---|---|
| Total Site Energy | 4388298.4 | 101.6 | 101.6 |
| Net Site Energy | 4388298.4 | 101.6 | 101.6 |
| Total Source Energy | 13897757.3 | 321.7 | 321.7 |
| Net Source Energy | 13897757.3 | 321.7 | 321.7 |
| Site=>Source Conversion Factor | |
|---|---|
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
Schedule Overview
| Schedule | Type Limits | Rules | Use Count |
|---|---|---|---|
| Air Velocity Schedule | Velocity | 0 | 11 |
| Always On | Dimensionless | 0 | 67 |
| CHW Temp | Temperature | 3 | 1 |
| Clothing Schedule | ClothingInsulation | 1 | 11 |
| CW Temp | Temperature | 3 | 1 |
| Make-up air unit Occ Sch | Dimensionless | 7 | 2 |
| Makeup-Air Unit Supply Air Temp | Temperature | 0 | 1 |
| NECB-A-Electric-Equipment | Dimensionless | 3 | 1 |
| NECB-A-Lighting | Dimensionless | 3 | 1 |
| NECB-A-Occupancy | Dimensionless | 3 | 1 |
| NECB-A-Service Water Heating | Dimensionless | 3 | 1 |
| NECB-A-Thermostat Setpoint-Cooling | Temperature | 3 | 3 |
| NECB-A-Thermostat Setpoint-Heating | Temperature | 3 | 3 |
| NECB-Activity | ActivityLevel | 0 | 67 |
| NECB-B-Electric-Equipment | Dimensionless | 3 | 2 |
| NECB-B-Lighting | Dimensionless | 3 | 2 |
| NECB-B-Occupancy | Dimensionless | 3 | 2 |
| NECB-B-Service Water Heating | Dimensionless | 3 | 2 |
| NECB-B-Thermostat Setpoint-Cooling | Temperature | 3 | 6 |
| NECB-B-Thermostat Setpoint-Heating | Temperature | 3 | 6 |
| NECB-C-Electric-Equipment | Dimensionless | 3 | 4 |
| NECB-C-Lighting | Dimensionless | 3 | 4 |
| NECB-C-Occupancy | Dimensionless | 3 | 4 |
| NECB-C-Thermostat Setpoint-Cooling | Temperature | 3 | 9 |
| NECB-C-Thermostat Setpoint-Heating | Temperature | 3 | 9 |
| NECB-E-Electric-Equipment | Dimensionless | 3 | 9 |
| NECB-E-Lighting | Dimensionless | 3 | 9 |
| NECB-E-Occupancy | Dimensionless | 3 | 9 |
| NECB-E-Service Water Heating | Dimensionless | 3 | 9 |
| NECB-E-Thermostat Setpoint-Cooling | Temperature | 3 | 19 |
| NECB-E-Thermostat Setpoint-Heating | Temperature | 3 | 19 |
| NECB-F-Electric-Equipment | Dimensionless | 3 | 50 |
| NECB-F-Lighting | Dimensionless | 3 | 50 |
| NECB-F-Occupancy | Dimensionless | 3 | 50 |
| NECB-F-Service Water Heating | Dimensionless | 3 | 35 |
| NECB-F-Thermostat Setpoint-Cooling | Temperature | 3 | 105 |
| NECB-F-Thermostat Setpoint-Heating | Temperature | 3 | 105 |
| NECB-H-Electric-Equipment | Dimensionless | 3 | 1 |
| NECB-H-Lighting | Dimensionless | 3 | 1 |
| NECB-H-Occupancy | Dimensionless | 3 | 1 |
| NECB-H-Service Water Heating | Dimensionless | 3 | 1 |
| NECB-H-Thermostat Setpoint-Cooling | Temperature | 3 | 3 |
| NECB-H-Thermostat Setpoint-Heating | Temperature | 3 | 3 |
| ON_OFF_ALWAYS_OFF | Availability | 3 | 42 |
| Schedule Ruleset 10 | 0 | 1 | |
| Schedule Ruleset 100 | 0 | 1 | |
| Schedule Ruleset 101 | 0 | 1 | |
| Schedule Ruleset 102 | 0 | 1 | |
| Schedule Ruleset 103 | 0 | 1 | |
| Schedule Ruleset 104 | 0 | 1 | |
| Schedule Ruleset 105 | 0 | 1 | |
| Schedule Ruleset 106 | 0 | 1 | |
| Schedule Ruleset 107 | 0 | 1 | |
| Schedule Ruleset 108 | 0 | 1 | |
| Schedule Ruleset 109 | 0 | 1 | |
| Schedule Ruleset 11 | 0 | 1 | |
| Schedule Ruleset 110 | 0 | 1 | |
| Schedule Ruleset 111 | 0 | 1 | |
| Schedule Ruleset 112 | 0 | 1 | |
| Schedule Ruleset 113 | 0 | 1 | |
| Schedule Ruleset 114 | 0 | 1 | |
| Schedule Ruleset 115 | 0 | 1 | |
| Schedule Ruleset 116 | 0 | 1 | |
| Schedule Ruleset 117 | 0 | 1 | |
| Schedule Ruleset 118 | 0 | 1 | |
| Schedule Ruleset 119 | 0 | 1 | |
| Schedule Ruleset 12 | 0 | 1 | |
| Schedule Ruleset 120 | 0 | 1 | |
| Schedule Ruleset 121 | 0 | 1 | |
| Schedule Ruleset 122 | 0 | 1 | |
| Schedule Ruleset 123 | 0 | 1 | |
| Schedule Ruleset 124 | 0 | 1 | |
| Schedule Ruleset 125 | 0 | 1 | |
| Schedule Ruleset 126 | 0 | 1 | |
| Schedule Ruleset 127 | 0 | 1 | |
| Schedule Ruleset 128 | 0 | 1 | |
| Schedule Ruleset 129 | 0 | 1 | |
| Schedule Ruleset 13 | 0 | 1 | |
| Schedule Ruleset 130 | 0 | 1 | |
| Schedule Ruleset 131 | 0 | 1 | |
| Schedule Ruleset 132 | 0 | 1 | |
| Schedule Ruleset 133 | 0 | 1 | |
| Schedule Ruleset 134 | 0 | 1 | |
| Schedule Ruleset 135 | 0 | 1 | |
| Schedule Ruleset 136 | 0 | 1 | |
| Schedule Ruleset 137 | 0 | 1 | |
| Schedule Ruleset 138 | 0 | 1 | |
| Schedule Ruleset 139 | 0 | 1 | |
| Schedule Ruleset 14 | 0 | 1 | |
| Schedule Ruleset 140 | 0 | 1 | |
| Schedule Ruleset 141 | 0 | 1 | |
| Schedule Ruleset 142 | 0 | 1 | |
| Schedule Ruleset 143 | 0 | 1 | |
| Schedule Ruleset 144 | 0 | 1 | |
| Schedule Ruleset 145 | 0 | 1 | |
| Schedule Ruleset 146 | 0 | 1 | |
| Schedule Ruleset 15 | 0 | 1 | |
| Schedule Ruleset 16 | 0 | 1 | |
| Schedule Ruleset 17 | 0 | 1 | |
| Schedule Ruleset 18 | 0 | 1 | |
| Schedule Ruleset 19 | 0 | 1 | |
| Schedule Ruleset 20 | 0 | 1 | |
| Schedule Ruleset 21 | 0 | 1 | |
| Schedule Ruleset 22 | 0 | 1 | |
| Schedule Ruleset 23 | 0 | 1 | |
| Schedule Ruleset 24 | 0 | 1 | |
| Schedule Ruleset 25 | 0 | 1 | |
| Schedule Ruleset 26 | 0 | 1 | |
| Schedule Ruleset 27 | 0 | 1 | |
| Schedule Ruleset 28 | 0 | 1 | |
| Schedule Ruleset 29 | 0 | 1 | |
| Schedule Ruleset 3 | 0 | 1 | |
| Schedule Ruleset 30 | 0 | 1 | |
| Schedule Ruleset 31 | 0 | 1 | |
| Schedule Ruleset 32 | 0 | 1 | |
| Schedule Ruleset 33 | 0 | 1 | |
| Schedule Ruleset 34 | 0 | 1 | |
| Schedule Ruleset 35 | 0 | 1 | |
| Schedule Ruleset 36 | 0 | 1 | |
| Schedule Ruleset 37 | 0 | 1 | |
| Schedule Ruleset 38 | 0 | 1 | |
| Schedule Ruleset 39 | 0 | 1 | |
| Schedule Ruleset 4 | 0 | 1 | |
| Schedule Ruleset 40 | 0 | 1 | |
| Schedule Ruleset 41 | 0 | 1 | |
| Schedule Ruleset 42 | 0 | 1 | |
| Schedule Ruleset 43 | 0 | 1 | |
| Schedule Ruleset 44 | 0 | 1 | |
| Schedule Ruleset 45 | 0 | 1 | |
| Schedule Ruleset 46 | 0 | 1 | |
| Schedule Ruleset 47 | 0 | 1 | |
| Schedule Ruleset 48 | 0 | 1 | |
| Schedule Ruleset 49 | 0 | 1 | |
| Schedule Ruleset 5 | 0 | 1 | |
| Schedule Ruleset 50 | 0 | 1 | |
| Schedule Ruleset 51 | 0 | 1 | |
| Schedule Ruleset 52 | 0 | 1 | |
| Schedule Ruleset 53 | 0 | 1 | |
| Schedule Ruleset 54 | 0 | 1 | |
| Schedule Ruleset 55 | 0 | 1 | |
| Schedule Ruleset 56 | 0 | 1 | |
| Schedule Ruleset 57 | 0 | 1 | |
| Schedule Ruleset 58 | 0 | 1 | |
| Schedule Ruleset 59 | 0 | 1 | |
| Schedule Ruleset 6 | 0 | 1 | |
| Schedule Ruleset 60 | 0 | 1 | |
| Schedule Ruleset 61 | 0 | 1 | |
| Schedule Ruleset 62 | 0 | 1 | |
| Schedule Ruleset 63 | 0 | 1 | |
| Schedule Ruleset 64 | 0 | 1 | |
| Schedule Ruleset 65 | 0 | 1 | |
| Schedule Ruleset 66 | 0 | 1 | |
| Schedule Ruleset 67 | 0 | 1 | |
| Schedule Ruleset 68 | 0 | 1 | |
| Schedule Ruleset 69 | 0 | 1 | |
| Schedule Ruleset 7 | 0 | 1 | |
| Schedule Ruleset 70 | 0 | 1 | |
| Schedule Ruleset 71 | 0 | 1 | |
| Schedule Ruleset 72 | 0 | 1 | |
| Schedule Ruleset 73 | 0 | 1 | |
| Schedule Ruleset 74 | 0 | 1 | |
| Schedule Ruleset 75 | 0 | 1 | |
| Schedule Ruleset 76 | 0 | 1 | |
| Schedule Ruleset 77 | 0 | 1 | |
| Schedule Ruleset 78 | 0 | 1 | |
| Schedule Ruleset 79 | 0 | 1 | |
| Schedule Ruleset 8 | 0 | 1 | |
| Schedule Ruleset 80 | 0 | 1 | |
| Schedule Ruleset 81 | 0 | 1 | |
| Schedule Ruleset 82 | 0 | 1 | |
| Schedule Ruleset 83 | 0 | 1 | |
| Schedule Ruleset 84 | 0 | 1 | |
| Schedule Ruleset 85 | 0 | 1 | |
| Schedule Ruleset 86 | 0 | 1 | |
| Schedule Ruleset 87 | 0 | 1 | |
| Schedule Ruleset 88 | 0 | 1 | |
| Schedule Ruleset 89 | 0 | 1 | |
| Schedule Ruleset 9 | 0 | 1 | |
| Schedule Ruleset 90 | 0 | 1 | |
| Schedule Ruleset 91 | 0 | 1 | |
| Schedule Ruleset 92 | 0 | 1 | |
| Schedule Ruleset 93 | 0 | 1 | |
| Schedule Ruleset 94 | 0 | 1 | |
| Schedule Ruleset 95 | 0 | 1 | |
| Schedule Ruleset 96 | 0 | 1 | |
| Schedule Ruleset 97 | 0 | 1 | |
| Schedule Ruleset 98 | 0 | 1 | |
| Schedule Ruleset 99 | 0 | 1 | |
| Service Water Loop Temp - 140F | Temperature | 0 | 2 |
| Supply Air Temp | Temperature | 0 | 1 |
| VAV with Reheat Occ Sch | Dimensionless | 7 | 2 |
| Water Heater Ambient Temp Schedule - 70F | Temperature | 0 | 1 |
| Work Efficiency Schedule | Dimensionless | 0 | 11 |